A (Optional) TN-C System Application
If the TN-C system is adopted, short-circuit the input N and PE, and connect the
input PE and N to terminals on the N bar.
Recommended cable cross-sectional area: 240 mm
2
Figure A-1 Short-circuiting the input N and PE
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) A (Optional) TN-C System Application
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 104