● The ECM provides module working status information to the monitoring
system.
● The ECM controls the running of a single UPS and a parallel system, and
reports the UPS status information to other monitoring modules.
● The system provides three types of CAN communication: monitoring CAN
communication, intra-rack parallel CAN communication, and inter-rack
parallel CAN communication.
● The control module consists of one active ECM and one standby ECM.
● Hot-swappable, 1 U high.
Figure 4-4 Appearance
Table 4-5 Port description
Silk Screen
Description
PARALLEL The PARALLEL port transmits parallel signals between racks.
BSC The BSC port is used in a dual-bus system to synchronize
output frequencies and phases between UPS systems,
ensuring that two buses can switch with each other.
BSC cables are hot-swappable.
 
No parallel cable is required for a single UPS.
Table 4-6 Indicator description
Indicator
Color Status Description
NORMAL Green Steady on This ECM is the active ECM.
Blinking at 0.5
Hz
This ECM is the standby ECM and it is
ready.
O This ECM is not ready or the software
of this ECM is being upgraded.
Blinking at 4 Hz The ECM software is being upgraded
or not congured.