NO TICE
A dry contact card port takes eect only after you set it in the software. You
need to disable unused dry contact signals.
Set the EPO port to normally open (NO) or normally closed (NC) as required.
If multiple UPSs are connected in parallel, connect all used dry contact signals
to each UPS.
Signal cables must be double-insulated twisted cables. If the cable length is
within 25–50 m, the cross-sectional area must be 0.5–1.5 mm
2
.
For dry contact outputs, the rated DC voltage and current are 24 V DC and 0.6
A and the maximum values are 30 V DC and 1.0 A. The rated AC voltage and
current are 24 V AC and 0.6 A and the maximum values are 30 V AC and 1.0 A.
During cable connection, ensure that the voltage and current do not exceed
these maximum values.
Figure 4-6 Appearance
Table 4-7 Functions of control signal ports on the dry contact card
Silk Screen
Signal Description Status
Description
Initial
Status
BTG Port for monitoring battery
grounding failures
Closed: There is
a battery
grounding
failure.
Open: There is
no battery
grounding
failure.
Open
0V Port for signal ground
GEN Port for detecting the diesel
generator (DG) mode
Closed: DG
mode
Open: non-DG
mode
Open
0V Port for signal ground
BCB_OL Port for monitoring the
battery circuit breaker (BCB)
box
Grounded: BCB
box connected
Disconnected:
BCB box not
connected
Grounde
d
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 4 Component Description
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 32