Table 4-12 Indicator status
Status Color Meaning
On Red A critical alarm has been generated, and the
buzzer sounds continuously.
Yellow A minor alarm has been generated, and the
buzzer buzzes intermittently at 2 Hz.
Green The UPS is running properly or a warning has
been generated.
O - The MDU is powered o.
NO TE
The indicator on the MDU panel is yellow when the bypass supplies power in non-ECO
mode.
Figure 4-14 MDU ports
Table 4-13 MDU port description
No.
Port Name Description
1 MUS05A
(DB26)
Connects to the MDU and monitoring interface card.
2 GE Network port
3 CAN Reserved
4 RS485_1 Reserved
5 FE_1 Reserved
6 FE_2 Reserved
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 4 Component Description
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 39