Item 400 kVA 500 kVA 600 kVA
N
PE 2×120 3×120 4×95
Bypass input Bypass input current
(A)
608 760 912
Recommende
d cross-
sectional area
(mm
2
)
L1 2 x (4 x
240)
2 x (4 x
240)
3 x (4 x
240)
L2
L3
N
PE 2×120 2×120 3×120
Output Output current (A) 608 760 912
Recommende
d cross-
sectional area
(mm
2
)
U 2 x (4 x
240)
2 x (4 x
240)
3 x (4 x
240)
V
W
N
PE 2×120 2×120 3×120
Battery
input (lead-
acid
battery)
Nominal battery
discharge current
(A)
887 1108 1330
Maximum battery
discharge current
(A)
1062 1327 1593
Recommende
d cross-
sectional area
(mm
2
)
+ 2 x (2 x
240)
3 x (2 x
185)
3 x (2 x
240)
-
PE 240 240 240
Battery
input
(SmartLi)
Nominal battery
discharge current
(A)
822 1028 1234
Maximum battery
discharge current
(A)
1032 1290 1547
Recommended
cross-sectional area
(mm
2
)
For details, see the IEC 60364-5-52
specications and SmartLi user manual.
UPS5000-H-(400 kVA-600 kVA)