2105 Model B09 Versatile Storage Server
Dimensions
Height 1780 mm 70.0 in.
Width 840 mm 33.0 in.
Depth 1305 mm 51.0 in.
Weight 746 kg 1640 lbs.
Electrical
Power source loading 3.4 kVA
Power factor 0.9
Voltage range (V ac) 200 to 480
Frequency (hertz) 50 or 60
Thermal output
(Maximum)
11600 Btu/hr
Maximum altitude 2135 m (7000 ft.)
Temperature
Requirements
(See note)
Operating
10 to 38°C
(50 to 90°F)
Non-Operating
10 to 43°C
(50 to 110°F)
Humidity
Requirements
Operating Non-Operating
(Noncondensing) 8 to 80% 8 to 80%
Wet Bulb 23°C (73°F) 27°C (80°F)
Noise Emissions¹ Operating
L
WAd
7.6 bels
Clearances Front Back Left Right
Service 1145 mm(45 in) 810 mm (32 in) N/A N/A
1. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
Note: The recommended operating temperature is 22°C (72°F) or lower. At lower temperatures, the risk of failure in
the unit is reduced. If the operating temperature is above 22°C (72°F) for long periods of time, the unit will be
exposed to a greater risk of failure from external causes.
238 Site and Hardware Planning Information