7026 Model M80 CEC Drawer
The Model M80 includes the Central Electronics Complex (CEC) Drawer with an I/O Drawer. For technical
information on the I/O Drawer, see “I/O Drawer 5 EIA” on page 79.
Dimensions
Height 355.6 mm 14.0 in.
Width 445.5 mm 17.5 in.
Depth 825.5 mm 32.5 in.
Weight
Minimum 69.7 kg 158 lbs.
Maximum 74.6 kg 169 lbs.
Electrical
Power source loading typical in kVA 0.39
Power source loading maximum in kVA 0.6
Voltage range (V ac) 200 to 240
Frequency (hertz) 50 or 60
Thermal output (typical) 1265 Btu/hr
Thermal output (maximum) 1877 Btu/hr
Power requirements (typical) 370 watts
Power requirements (maximum) 550 watts
Power factor 0.95
Inrush current³ 34 amps
Maximum altitude 2135 m (7000 ft.)
Temperature Requirements Operating
10 to 40°C
(50 to 104°F)
Non-Operating (Power Off)
10 to 52°C
(50 to 125°F)
Humidity (Noncondensing) Operating Non-Operating (Power Off)
Without tape drive 8 to 80% 8 to 80%
With tape drive 20 to 80% 8 to 80%
Wet Bulb Requirements
Without tape drive 27°C (80°F) 27°C (80°F)
With tape drive 27°C (80°F) 27°C (80°F)
Noise Emissions
1,2
Operating Idle
With M80 CEC Drawer only
L
WAd
6.4 bels 6.4 bels
L
pAm
N/A N/A
<L
pA
>
m
48 dBA 48 dBA
Impulsive or prominent discrete tones No No
Noise Emissions
1,2
Operating Idle
With M80 and Primary I/O Drawer
L
WAd
6.5 bels 6.5 bels
L
pAm
N/A N/A
<L
pA
>
m
49 dBA 49 dBA
Impulsive or prominent discrete tones No No
Install/Air Flow Clearance Maintenance of a proper service clearance should allow proper air flow.
Service Clearance (See service clearances for the 7014 T00 Rack)
1. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
2. Noise emissions data are based on the following configuration: a drawer is in a T00 Rack and a power
distribution unit is installed in the rack and the system is operating in a normal environment of 25 °C (78 °F)
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
78 Site and Hardware Planning Information