v Fan failures in the power supplies
v Defective circuitry in a power supply
v Blocked air vents
v Failures in other devices in the configuration or rack
If a fan failure causes overheating, the system-error LED and overtemperature
LEDs on the storage subsystem are lit. The fault LED on the power supply might
also be lit. “Checking the LEDs” on page 73 shows the location of the LEDs on the
DS3500.
If the storage subsystem temperature exceeds 45°C (113°F), the storage
management software displays a Needs Attention icon in the Subsystem
Management window. If the air temperature inside the rack reaches 65°C (149°F),
the power supplies automatically shut down. If event monitoring is enabled and
event notification is configured, the software issues two critical-problem notifications.
v If one power supply shuts down, the storage management software displays a
Needs Attention status in the Subsystem Management window.
v If both power supplies shut down, the storage subsystem shuts down, and the
storage management software displays a Not Responding status in the Array
Management window.
Attention: To prevent damage to the storage subsystem components when the
power supplies automatically shut down, immediately remove all rack panels to
help reduce the rack air temperature.
To resume normal operation after a power-supply shutdown, complete the following
steps:
1. Did you use the procedure “Troubleshooting the storage subsystem” on page
72 to identify an overheating problem?
v Yes: Go to step 2.
v No: Perform the procedure in “Troubleshooting the storage subsystem” on
page 72 to make sure that the power supplies have shut down because of
an overheating problem, and then go to step 2.
2. Stop I/O activity to the storage subsystem and all attached expansion
enclosures.
3. Take all or some of the following measures to alleviate the overheating
problem:
v Remove all panels from the rack immediately.
v Use external fans to cool the area.
v Shut down the power to the expansion enclosure, using the procedure that
is described in “Performing an emergency shutdown” on page 83.
4. Wait for the air in and around the storage subsystem to cool.
After the temperature inside the power supplies drops to below 65°C (149°F),
the storage subsystem is capable of power-on recovery without operator
intervention. After the air has cooled, the power supplies should turn on
automatically. If the power supplies restart automatically, the controllers will
reset and return to normal operation.
5. Did the power supplies restart automatically?
v Yes: Go to step 8 on page 86.
v No: Go to step 6 on page 86.