3.9 Menu – Cascade manager
The cascade manager menu has the
followingsubmenus:
Cascade manager
Status
Operating Mode
Settings
3.9.1 Menu – Cascade manager -
Status
Onselectingstatus,thefollowingsubmenus
areavailable:
Cascade manager
Summary
Boilers
Thiswill now showthe status of theplant
cascade,andeachboilerinthecascade.
3.9.2 Menu – Cascade manager –
Status – Summary
Summary shows the actual heat capacity
being generated and the target calculated
requirement.
Summary
Actual: 0%
Requested: 0%
3.9.3 Menu – Cascade manager –
Status – Boilers
Summaryshowstheactualoperatingmode
andheatcapacitybeinggeneratedbyeach
boiler,thelistcanbescrolledifrequiredto
showallboilerscongured:
Boilers
Boiler 1: Off, 0%
Boiler 2: Off, 0%
3.9.4 Cascde Manager - Operating
mode
TheCascadeboilersequencecontrolcanbe
settooneofthreecontrolmethods.Select
theeldinordertoscrollthroughthethree
options.
Hours run - The sequence changeover
isdeterminedbythe number of burner-on
hours.Thehoursrunvaluecanbeadjusted
intheSettingsmenu.
Operating mode
Hours run
Done
Fixed Order-Thesequencechangeover
orderisxed.
Operating mode
Fixed order
Done
Timed-Thesequencechangeoveris
determinedbyoperatingtimeperiod.The
periodcanbeadjustedintheSettings
menu.
Operating mode
Timed
Done
Onceselected,selectDonetoconrm.
Operating mode
Timed
Done
3.9.5 Menu – Cascade manager –
Settings
Thesettingsmenuwillhavecontentbased
uponconguration of aSlaveheatsource
andtheselectedCascadeOperatingmode.
HoursrunorTimed.
Alloptionsareshownbelow,butnotallmay
be present.
Settings
Boiler modulation
Sequence on delay
Hours run
Settings
Boiler modulation
Sequence on delay
Hours run
Sequence order
Settings
Sequence on delay
Hours run
Sequence order
Timed
Settings
Hours Run
Sequence order
Timed
Ext. heat source sequence
Settings
Sequence order
Timed
Ext. heat source sequence
Settings
Timed
Ext. heat source sequence
3.9.6 Menu – Cascade manager –
Settings – Boiler modulation
Boiler modulation controls the switching
capacity set points in the cascade. Each
boilerincascadecanbeswitchedonatthe
earliest or latest modulation capacity set
point(modulationmax.),aswellasswitched
offinthesameway(modulationmin.).
Boiler modulation
Modulation max.
Modulation min.
3.9.7 Modulation max
Thiscausestherstboilerinthesequenceto
modulateuptotheModulationmaxcapacity
settingbeforeitbringsonthesecondboiler
inthesequenceandthenmodulatesdown
tomatchthecapacityofboth.Thiscontinues
foreachboiler.
Modulation max.
80%
3.9.8 Modulation min
Thiscausesthecascadetomodulatedown
totheModulationminsettingoneachboiler
beforeswitchingoneoff.Thisthencontinues
foreachboiler.
Modulation min.
30%
3.9.9 Menu – Cascade manager –
Settings – Sequence on delay
This parameter sets the time delay when
bringing on boilers in sequence, this is to
allowfortheboilercascadetobettermatch
theloadduringthestartofademandcycle.
Sequence on delay
10secs
3.9.10 Menu – Cascade manager –
Settings – Sequence order
Theorderthattheboilersruninsequence
canbeset,thisdoesnotaffecttheleadboiler
rotation.To change the order,remove the
boilernumbersinsequencebysettingthem
toNNandthenredenetheboilernumbers
as required. By default the boiler number
followsthesequencenumber.
Sequence order
Seq. 1: Boiler 01
Seq. 2: Boiler 02