5.3 Plant Conguration
Congure plant?
No
Yes
Plant configuration is related to shared
resourcesnecessaryfortheoperationofthe
completecascade/plant.To congure these
select‘Yes’andthenfollowthescreens.
Hydraulic Separation:
IftheboilerhasHydraulicSeparationfrom
theintermediateornalcircuitsintheheating
system,oriftheboilershaveacombinedue
systemthensetthisoptiontoeither‘Header’
or‘Plateheatexchanger’.
Hydraulic separation?
No
Header
Plate heat exchanger
Hydraulic separation?
No
Header
Plate Heat exchanger
Hydraulic separation?
Header
Plate heat exchanger
Header Thermistor:
If the system has a header sensor tted,
combinedow,thenselect‘Yes’,otherwise
the system will use the average flow
temperature of all running boilers.
Set Flue System:
Iftheboilersareconnectedintoacommon
orcascadeuesystemthenyoucanchoose
multiline ue system where the minimum
capacityoftheboilerinacascadecanbe
increasedinordertoensurenobackowin
theuesystem.
Set ue system
Standard
Multiline
Set ue system
Standard
Multiline
Iftheboilercascadehasacommonpump
thatcirculateswaterthroughalltheboilers
in the Cascade the select the output of
the Master boiler that controls this pump.
Otherwiseselect‘None’.
Loc’n of shared boiler pump?
None
PWM/0-10V ()
MFR1 ()
Thefollowingoutputscanbeconguredfor
thisfunction:
Loc’n of shared boiler pump?
None
PWM/0-10V ()
MFR1 ()
MFR2 ()
Loc’n of shared boiler pump?
PWM/0-10V ()
MFR1 ()
MFR2 ()
MFR3 ()
Loc’n of shared boiler pump?
MFR1 ()
MFR2 ()
MFR3 ()
MFR4 ()
Loc’n of shared boiler pump?
MFR2 ()
MFR3 ()
MFR4 ()
Loc’n of shared boiler pump?
MFR3 ()
MFR4 ()
Note: Once a programmable has been
selectedthefunctionwillappearwithinthe
parenthesis at the right of the designated
output name.
Iftheboilercascadehasacommonpump
thatcirculateswaterthrougheithertheboiler
cascade or cascade header and supplies
the heating load then select the output of
the Master boiler that controls this pump.
Otherwiseselect‘None’.
Select Loc’n of system pump?
None
PWM/0-10V ()
MFR1 ()
Thefollowingoutputscanbeconguredfor
thisfunction:
Select Loc’n of system pump?
None
PWM/0-10V ()
MFR1 ()
MFR2 ()
Select Loc’n of system pump?
PWM/0-10V ()
MFR1 ()
MFR2 ()
MFR3 ()
Select Loc’n of system pump?
MFR1 ()
MFR2 ()
MFR3 ()
MFR4 ()
Select Loc’n of system pump?
MFR2 ()
MFR3 ()
MFR4 ()
Select Loc’n of system pump?
MFR3 ()
MFR4 ()
Iftheboilercascadehasashunt pumpto
control the temperature differential of the
cascadeowtoreturnthenselecttheoutput
oftheMasterboilerthatcontrolsthispump.
Otherwiseselect‘None’.
Select Loc’n of shunt pump?
None
PWM/0-10V ()
MFR1 ()
Thefollowingoutputscanbeconguredfor
thisfunction:
Select Loc’n of shunt pump?
None
PWM/0-10V ()
MFR1 ()
MFR2 ()
Select Loc’n of shunt pump?
PWM/0-10V ()
MFR1 ()
MFR2 ()
MFR3 ()
Select Loc’n of shunt pump?
MFR1 ()
MFR2 ()
MFR3 ()
MFR4 ()