77
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
Error
Code
Anomaly signalled Cause Boiler status / Solution
08 Maximum N° of resets Number of allowed resets already performed.
e anomaly can be reset 5 times
consecutively, aer which the
function is inhibited for at least one
hour. One attempt is gained every
hour for a maximum of 5 attempts. By
switching the appliance on and o
again, the 5 attempts are re-acquired.
10
Insucient system
pressure
Water pressure inside the central heating circuit that is suf-
cient to guarantee the correct operation of the boiler is not
detected.
Check on the boiler pressure gauge
that the system pressure is between
1÷1.2 bar and restore the correct
pressure if necessary.
12
Storage tank probe
anomaly
e board detects a fault on the storage tank probe (when
paired with a storage tank unit).
e boiler cannot produce domestic
hot water (1).
15 Conguration error
If the board detects an anomaly or incongruity on the elec-
tric wiring, the boiler will not start.
If normal conditions are restored the
boiler restarts without having to be
reset. Check that the boiler is cong-
ured correctly (1).
16 Fan anomaly is occurs if the fan has a mechanical or electrical fault. Press the Reset button (1).
20 Parasite ame block
is occurs in the event of a leak on the detection circuit or
anomaly in the ame control unit.
Press the Reset button (1).
23
Return probe
anomaly
e board detects an anomaly on the return NTC probe. e boiler does not start (1).
24
Push button control
panel anomaly
e board detects an anomaly on the pushbutton panel.
If normal conditions are restored the
boiler restarts without having to be
rese t (1).
29 Flue probe anomaly e board detects an anomaly on the ue gas probe. e boiler does not start (1).
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Service Centre)
(2) e anomaly can only be veried in the list of errors in the “Information” menu