6.6 DNP3.0
The following table provides a “Device Prole Document” in the standard format dened in the
DNP3 Subset Denitions Document. While it is referred to in the DNP3 Subset Denitions as a
“Document,” it is only a component of a total interoperability guide. This table in combination with
the Implementation Table should provide a complete interoperability/conguration guide for the
OPTImizer
2
.
6.6.1 Device Prole Document
DNP V3.0
Device Prole Document
(Also see the DNP Implementation Table, beginning on page 68)
Vendor Name: Franklin Fueling Systems, Inc.
INCON Power Reliability Systems
Device Name: OPTImizer
2
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
1 Master
g Slave
Notable objects, functions, and/or qualiers supported in addition to the Highest DNP Levels Supported (the
complete list is described in the Implementation Table):
NONE
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets):
Transmitted: Fixed at 4096
Received: Fixed at 4096
Maximum Data Link Re-tries:
1 None
1 Fixed
g Congurable from 0 to 255
Maximum Application Layer Re-tries:
1 None
g Congurable from 0 to 65535
Requires Data Link Layer Conrmation:
1 Never
1 Always
g Sometimes
1 Congurable
Requires Application Layer Conrmation:
1 Never
1 Always
g Sometimes
1 Congurable
Timeouts while waiting for:
Data Link Conrm: 1 None g Fixed at 1 sec. 1 Variable 1 Congurable
Complete Appl. Fragment 1 None g Fixed at 5 sec. 1 Variable 1 Congurable
Application Conrm: 1 None g Fixed at 5 sec. 1 Variable 1 Congurable
Complete Appl. Response: 1 None g Fixed at 5 sec. 1 Variable 1 Congurable