EasyManua.ls Logo

Incon OPTImizer 2 - DNP3.0 Point List

Incon OPTImizer 2
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
69
6.6.3 DNP3.0 Point List
The following table identies for each data type, the data points available in the device.
Binary Input Points Slave >> Master
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: 1 (Binary Input 2 without status)
Change Event Variation reported when variation 0 requested: 3 (Binary Input Change with Time)
Event
Class
Point
Index
Default
Group
Default
Variable
Name/Description
Circuit Breaker Monitor
1 0 2 2
Breaker Is Open
1 1 2 2
A-B Logic Failure Alarm Acve
1 2 2 2
Contact Life Warning Acve Phase A
1 3 2 2
Contact Life Warning Acve Phase B
1 4 2 2
Contact Life Warning Acve Phase C
1 5 2 2
Contact Life Danger Alarm Acve Phase A
1 6 2 2
Contact Life Danger Alarm Acve Phase B
1 7 2 2
Contact Life Danger Alarm Acve Phase C
1 8 2 2
Trip Time Alarm Acve
1 9 2 2
Arc Time Alarm Acve Phase A
1 10 2 2
Arc Time Alarm Acve Phase B
1 11 2 2
Arc Time Alarm Acve Phase C
1 12 2 2
Clearing Time Alarm Acve Phase A
1 13 2 2
Clearing Time Alarm Acve Phase B
1 14 2 2
Clearing Time Alarm Acve Phase C
1 15 2 2
Travel Time Alarm Acve
1 16 2 2
Closing Time Alarm Acve
1 17 2 2
Operaon Count Alarm Acve
1 18 2 2
No-Operaons Alarm Acve
1 19 2 2
Restrike Alarm Acve Phase A
1 20 2 2
Restrike Alarm Acve Phase B
1 21 2 2
Restrike Alarm Acve Phase C
SF
6
Monitor
1 22 2 2
Sensor Malfuncon Alarm Acve
1 23 2 2
Low Density Alarm Acve
1 24 2 2
Trend Alarm Acve
1 25 2 2
CT Failure Alarm Acve Phase A
1 26 2 2
CT Failure Alarm Acve Phase B
1 27 2 2
CT Failure Alarm Acve Phase C
30 5 Default Static Analog
32 5 Default Event Analog
20 1 Default Static Counter
22 1 Default Event Counter
1 2 Default Static Binary
2 2 Default Event Counter

Table of Contents