70
Analog Input Points Slave >> Master
Static (Steady-State) Object Number: (30,1)
Change Event Object Number: (32,1)
Static Variation reported when variation 0 requested: (30,1)
Change Event Variation reported when variation 0 requested: (32,1)
Event
Class
Point
Index
Default
Group
Default
Variable
Name/Description Dead Band
Circuit Breaker Monitor
2 0 32 5
Current Wear Phase A
0
2 1 32 5
Current Wear Phase B
0
2 2 32 5
Current Wear Phase C
0
2 3 32 5
Percent of Warning Limit Phase A
0
2 4 32 5
Percent of Warning Limit Phase B
0
2 5 32 5
Percent of Warning Limit Phase C
0
2 6 32 5
Percent Of Danger Limit Phase A
0
2 7 32 5
Percent Of Danger Limit Phase B
0
2 8 32 5
Percent Of Danger Limit Phase C
0
2 9 30 5
Percent Remaining Contact Life Phase A
0
2 10 30 5
Percent Remaining Contact Life Phase B
0
2 11 30 5
Percent Remaining Contact Life Phase C
0
0 12 30 5
RMS Current Phase A
0
0 13 30 5
RMS Current Phase B
0
0 14 30 5
RMS Current Phase C
0
0 15 30 5
Days since last operaon
0
SF
6
Monitor
0 16 30 5
Current Density Channel A
0
0 17 30 5
Current Density Channel B
0
0 18 30 5
Current Density Channel C
0
0 19 30 5
Current Temperature Channel A
0
0 20 30 5
Current Temperature Channel B
0
0 21 30 5
Current Temperature Channel C
0
0 22 30 5
Trend Channel A
0
0 23 30 5
Trend Channel B
0
0 24 30 5
Trend Channel C
0
0 25 30 5
Trend Condence Level Channel A
0
0 26 30 5
Trend Condence Level Channel B
0
0 27 30 5
Trend Condence Level Channel C
0
0 28 30 5
Average Mass Channel A
0
0 29 30 5
Average Mass Channel B
0
0 30 30 5
Average Mass Channel C
0
0 31 30 5
Average Pressure Channel A
0
0 32 30 5
Average Pressure Channel B
0
0 33 30 5
Average Pressure Channel C
0