71
Counter Input Points Slave >> Master
Static (Steady-State) Object Number: (20,1)
Change Event Object Number: (22,1)
Static Variation reported when variation 0 requested: (20,1)
Change Event Variation reported when variation 0 requested: (22,1)
Point
Index
Point
Index
Default
Group
Default
Variable
Name/Description
1 0 22 1
Current Operaon Number
1 1 22 1
Operaon Count
Control Output Points Master >> Slave
Static (Steady-State) Object Number: (12,1)
Change Event Object Number: NA
Static Variation reported when variation 0 requested: NA
Change Event Variation reported when variation 0 requested: NA
Point
Index
Name/Description
Circuit Breaker Monitor
0
Clear Circuit Breaker Alarms
1
Reset Operaon Count
2
Preset Operaon Number
3
Preset Contact Life
SF
6
Monitor
4
Clear SF
6
Alarms
5
Reset Trend Data
Setpoint Output Points Master >> Slave
Static (Steady-State) Object Number: (40,2)
Change Event Object Number: NA
Static Variation reported when variation 0 requested: NA
Change Event Variation reported when variation 0 requested: NA
Circuit Breaker Monitor
0
Preset Operaon Number Value
1
Preset Contact Life Value Phase A
2
Preset Contact Life Value Phase B
3
Preset Contact Life Value Phase C