EasyManua.ls Logo

Incon OPTImizer 2 - Page 71

Incon OPTImizer 2
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
71
Counter Input Points Slave >> Master
Static (Steady-State) Object Number: (20,1)
Change Event Object Number: (22,1)
Static Variation reported when variation 0 requested: (20,1)
Change Event Variation reported when variation 0 requested: (22,1)
Point
Index
Point
Index
Default
Group
Default
Variable
Name/Description
1 0 22 1
Current Operaon Number
1 1 22 1
Operaon Count
Control Output Points Master >> Slave
Static (Steady-State) Object Number: (12,1)
Change Event Object Number: NA
Static Variation reported when variation 0 requested: NA
Change Event Variation reported when variation 0 requested: NA
Point
Index
Name/Description
Circuit Breaker Monitor
0
Clear Circuit Breaker Alarms
1
Reset Operaon Count
2
Preset Operaon Number
3
Preset Contact Life
SF
6
Monitor
4
Clear SF
6
Alarms
5
Reset Trend Data
Setpoint Output Points Master >> Slave
Static (Steady-State) Object Number: (40,2)
Change Event Object Number: NA
Static Variation reported when variation 0 requested: NA
Change Event Variation reported when variation 0 requested: NA
Circuit Breaker Monitor
0
Preset Operaon Number Value
1
Preset Contact Life Value Phase A
2
Preset Contact Life Value Phase B
3
Preset Contact Life Value Phase C

Table of Contents