3 Electrical Installation
- 67 -
Table 3-4 Main circuit cable selection for MD880-01S-0024-4-B/MD880-01S-0033-4-B
AC Drive
Model
Rated
Current
(A)
Recommended
Input/Output
Power Cable
(mm
2
)
Recommended
Lug Model
Recommended
Grounding
Cable (mm
2
)
Recommended
Grounding
Cable Lug
Model
Tightening
Torque
(N·m)
MD880-01S-
0024-4-B
24.0 3 x 4 TVR 5.5-5 4 TVR 5.5-5 2.5
MD880-01S-
0033-4-B
33.0 3 x 6 GTNR 6-5 6 GTNR 6-5 2.5
.
TDSFXT
Figure 3-26 MD880-01S-0038-4-B
Table 3-5 Main circuit cable selection for MD880-01S-0038-4-B
AC Drive
Model
Rated
Current
(A)
Recommended
Input/Output
Power Cable
(mm
2
)
Recommended
Lug Model
Recommended
Grounding
Cable (mm
2
)
Recommended
Grounding
Cable Lug
Model
Tightening
Torque
(N·m)
MD880-01S-
0038-4-B
38.0 3 x 10 GTNR 10-6 10 GTNR10-6 2.5