3 Electrical Installation
- 69 -
Table 3-8 Main circuit cable selection for MD880-01S-0116-4-B/MD880-01S-0149-4-B
AC Drive
Model
Rated
Current
(A)
Recommended
Input/Output
Power Cable
(mm
2
)
Recommended
Lug Model
Recommended
Grounding
Cable (mm
2
)
Recommended
Grounding
Cable Lug
Model
Tightening
Torque
(N·m)
MD880-01S-
0116-4-B
116 3 x 25 GTNR25-8 25 GTNR25-8 10.5
MD880-01S-
0149-4-B
149 3 x 50 GTNR50-8 25 GTNR25-8 10.5
.
OVUTBOE珞BUBOETQSJOHXBTIFST