DA180 series basic AC servo drive Function codes
-99-
If the absolute voltage value of analog input 2 falls in the range of this parameter, the
corresponding command value is 0.
This parameter specifies the internal torque reference. If the servo motor rated torque is
considered as 100%, the setting of this parameter is a percentage of the servo motor rated torque.
Note:
If the absolute value of this parameter is greater than maximum torque limit 1 (P0.10), the
output torque is the setting of P0.10 and the direction is the same as this parameter.
In torque mode, this parameter is valid only when P0.60 is 0.
This parameter specifies the speed limit mode for torque control.
The analog input is selected as the speed limit source. You need to set
either P3.26 [Function of AI 1] or P3.27 [Function of AI 2] to 1 [Speed limit]
and set associated parameters according to the actual situation.
Internal speed limit, selected from P0.46–P0.49.
Note: The speed limit is internally processed as an absolute value, and the actual sign of the limit
is the same as that of the torque command.
This parameter is used to modify the planning curve when the torque command input changes.
This parameter indicates the time taken to rise from 0 to 100% of the rated torque.