Goodrive35 Series Closed-loop Vector Control VFD Function parameters
65
Detailed instruction of parameters
Setting range: -300.0%–300.0% (rated current of the
motor)
Torque reference
filter time
Upper frequency of
forward rotation in
vector control
0: Keypad (P03.16 sets P03.14, P03.17 sets
P03.15)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDI setting upper-limit frequency
5: Multi-step setting upper-limit frequency
6: Modbus communication setting upper-limit
frequency
7: PROFIBUS/CANopen communication setting
upper-limit frequency
8: Ethernet communication setting upper-limit
frequency
Note: Setting method 0–8, 100% corresponds to the
maximum frequency
Upper frequency of
reverse rotation in
vector control
Keypad setting for
upper frequency of
forward rotation
This function is used to set the upper limit of the
frequency. P03.16 determines the setting when
P03.14=1; P03.17 determines the setting when
P03.15=1.
Setting range: 0.00 Hz–P00.03 (max. output
frequency)
Keypad setting for
upper frequency of
reverse rotation
Upper electromotion
torque source
This function code is used to select the
electromotion and brake torque upper-limit setting
source selection.
0: Keypad setting upper-limit frequency (P03.20 sets
P03.18, P03.21 sets P03.19)
1: AI1
2: AI2
3: AI3
4: HDI
5: Modbus communication
6: PROFIBUS/CANopen communication
7: Ethernet communication
Note: setting mode 1–7,100% corresponds to three
times of the motor current.
Upper brake torque
source