Inxpect SRE 200 Series| Instruction manual v1.5 DEC 2023 |Inxpect SAF-IM-200S_5m_7_00047_en_v1.5|© 2021-2023 Inxpect SpA
3. Get to know Inxpect SRE 200 Series
Case 3
Both digital inputs have been configured as Dynamic configuration switch,andthe encoded channel option is
disabled.
Dynamic
configuration
number
Input 1 (CH1 and
CH2)
Input 2 (CH1 and
CH2)
#1 0 0
#2 1 0
#3 0 1
#4 1 1
0 = signal deactivated; 1 = signal activated
Case 4
Both digital inputs have been configured as Dynamic configuration switch, andthe encoded channel option is
enabled.
The valid combinations are only those that differ at least by two values, and they are listed below:
Dynamic
configuration
number
Input 1 Input 2
CH1 CH2 CH1 CH2
#1 1 0
0
0
#2 0 1
0
0
#3 0 0
1
0
#4 0 0
0
1
#5 1 1 1 0
#6 1 1 0 1
#7 1 0 1 1
#8 0 1 1 1
0 = signal deactivated; 1 = signal activated
3.10.6 Dynamic configuration through the safety Fieldbus
To activate one of the preset configurations dynamically, connect an external safety PLC that communicates
through the safety Fieldbus to the control unit. This makes it possible to dynamically switch between all the
preset configurations, therefore up to 32 different configurations. For all the parameters used for each
configuration, see "Dynamic system configuration" on page34.
For details about the supported protocol, please refer to the Fieldbus manual.
WARNING! Before activating one of the preset configurations through the safety Fieldbus, ensure
that none of the digital inputs is configured as Dynamic configuration switch; otherwise, the Inxpect
SRE 200 Series ignores all the switches made through the safety Fieldbus.
3.10.7 Safe configuration change
The change of the configuration takes place safely both on stationary and moving machinery. The sensor always
monitors the entire monitored area and when it receives a request to change to a configuration with a longer
detection field, it immediately reverts to safe state if people are present in such a field.