EasyManuals Logo

ITC VA-6000 Series User Manual

ITC VA-6000 Series
135 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
Digital Network Public Address & Voice Alarm System
- 76 -
11. DC24V battery
12. Speaker (short circuit or open circuit)
13. The speaker (ground fault)
Through Setting on host VA-6000MA and software VA-6000ST, users can enable or disable the above
detection on monitoring events.
The operation steps of starting and forbidding module detection in VA-6000MA and PC.
VA-6000 system can perform real-time detection and monitor to all the online equipments it connects.
The detection and monitor must be conducted on the basis that the system is rightly configured and
connected, as well as the detection & monitor switch of all the equipments and modules are switched on.
Otherwise, the system will not perform detection and monitor steps. The system will take all states as
normal.
1. The operation steps of starting and forbidding module detection in VA-6000MA
Click on LOGO Standby Interface →enter into Main Menu click on →enter into User Identity
Checking Interface enter login password(default password is 666666) click on →enter
into System Setting Main Menu click on enter into Equipment
Detection Switch click on . By following the above steps, you can make the system start the
operation of detection and monitor function. If you want to ban the detection and monitor operation, click
on to make it .After banning that operation, the system will regard it normally working even if
the equipment is malfunctioned.
Malfunction example: Connection malfunction
Suppose that there is malfunction in the connection between VA-6000RM and VA-6000MA. When the
malfunction is detected, the system will have the following situations:
1. The buzzer in VA-6000MA will ring on, the system indicator will turn to yellow and flash, and the LCD
screen will show the malfunction.
2. The buzzer in VA-6000RM will ring on, and the system state indicator will turn to yellow and flash.