64 Installation—Installing the FC-2000
IZM-8 Zone 4: Program zone as non-alarm and supervisory. Provides a
simple evacuation function for non-voice alarm systems. All Call does not
perform telephone functions, but, rather, initiates an All Call function that
activates all silenceable circuits that are not programmed for switch
inhibit. When Zone 4 returns to normal, the CPU will deactivate the All
Call function (re-execute all zone-to-output mapping). Indicating
appliance circuits that should not activate during All Call (general alarm)
must be programmed for non-silenceable and/or switch inhibit operation.
IZM-8 Zone 5: Program zone as non-alarm and supervisory. Use as an
evacuation signal for tornadoes, bomb-scares and other non-fire
emergency situations. If the FC-2000 is not in alarm, activation (short) on
Zone 5 will activate all indicating appliance circuits and output relays
mapped to Zone 5 with a steady signal. Programmed March Time or
Temporal code is ignored. A fire alarm will take priority over an
emergency alert. Indicating appliance circuits used for fire must be
programmed for MTC or Code 3 operation. Emergency Alert is for local
signaling only, do not map to Remote Signaling/Municipal Tie outputs.
IZM-8 Zone 6: Program circuit as non-alarm and supervisory. Use to
remotely execute an Acknowledge command without the need of an
ACM-16AT annunciator.
IZM-8 Zone 7: Program circuit as non-alarm and supervisory. Use to
remotely execute the Signal Silence command without the need of an
ACM-16AT annunciator.
IZM-8 Zone 8: Program circuit as non-alarm and supervisory. Use to
execute the Reset function without the need of an ACM-16AT
annunciator.
All Call (General
Alarm)
Emergency Alert
Acknowledge
Signal Silence
System Reset

Table of Contents

Other manuals for Johnson Controls MPS-24A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls MPS-24A and is the answer not in the manual?

Johnson Controls MPS-24A Specifications

General IconGeneral
BrandJohnson Controls
ModelMPS-24A
CategoryControl Panel
LanguageEnglish

Related product manuals