Important: You must test all the smoke detectors yearly.
Performing a keypad and siren test
To perform a keypad and siren test, complete the following steps:
1. On the keypad, press * 6.
2. Enter your access code.
3. Use the Arrow keys to navigate to System Test, and press *. All keypad sounders, bells, sirens,
and keypad LEDs activate for 2 seconds.
4. Press # to return to the ready state.
Monitoring
This system is capable of transmitting alarms, troubles and emergency information. If an alarm is
initiated by mistake, immediately call the central station to prevent an unnecessary response.
Note: For CP-01 systems, the monitoring function must be enabled by the installer before it
is operational. There is a communicator delay of 30 seconds in this control panel. It can be
removed, or it can be increased up to 45 seconds, at the option of the end-user by consulting
with the installer. Fire type alarms are normally reported without a delay.
Maintenance
Keep your alarm controller in optimal condition by following the instructions included within this
manual and/or marked on the product. The end user and/or installer are responsible for disposing
of used batteries according to local waste recovery and recycling regulations.
• Use the system test described in “Testing the System” to check the battery condition. For
optimal performance, replace the standby batteries every 3-5 years.
• For other system devices such as smoke detectors, motion detectors or glassbreak detectors,
consult the manufacturer’s literature for testing and maintenance instructions.
• Lightly dust the security equipment with a slightly moistened cloth.
Note: Do not use abrasives, thinners, solvents or aerosol cleaners (spray polish) that may enter
through holes in the Alarm Controller and cause damage. Do not wipe the front cover with
alcohol, water or any other liquid.
Applicable models
This publication covers the following models:
Note: The X character refers to one of the following PG device operating frequencies: 4 refers to
433MHz, 8 refers to 868MHz, and 9 refers to 912-919MHz UL/ULC systems.
• HS3032
• HS3128
• HS3248
• HS2LCDPRO
• HS2LCDRFPROx
• HS2LCDWFPROx
• HS2LCDWFVPROx
PowerSeries Pro HS3032/HS3128/HS3248 User Manual10