must contact the monitoring station and provide the code that's displayed on the keypad. The
monitoring station operator will provide a different 5-digit code that the user can enter at the
system keypad, which will clear the remote reset condition, allowing the panel to be armed again.
Some user functions are still available while the system is locked out. The user can loan the keypad
to a different partition, and can access [*][6] User Functions so the event buffer can be reviewed to
determine cause of the alarm condition. The [*][3] Alarms in Memory and [*][7] command output
menus are also available during the remote reset condition.
This feature is intended to be used with burglary zones. Fire alarms do not generate remote reset.
Each partition will generate a unique Remote Reset code on the system keypads and must be
unlocked separately.
Initiating a walk test
This feature allows the user to verify the operation of system detectors and notify the central
station that a Walk Test is in progress.
Note: The installer must configure this feature.
Important: During a system (walk) test, do not activate any:
• Fire, Auxiliary or Police buttons
• Fire or CO sensors
A full system test is comprised of activating each sensor in turn. Open each door, window and walk
in areas with motion detectors. Perform system tests during off-peak hours, such as early morning
or late evening. When a test is in progress, the Ready, Trouble and Armed LEDs flash.
To initiate a walk test, complete the following steps:
1. On the keypad, press * 6.
2. Enter your access code.
3. Use the Arrow keys to navigate to Walk Test.
4. Press *. The system activates all the keypad sounders, bells, and sirens for two seconds. The
system sends a notification to inform the central station that a walk test has started.
5. Trigger each zone or detector by sequence. The keypad sounds, all LEDs on the keypad flash,
and the system records the event in the event buffer.
6. Restore the zones.
7. To end the walk test, complete the following steps:
a. Press* 6.
b. Enter your access code.
c. Press 8.
Note: Fire zones, the F key, and 2-wire smoke detectors are excluded from the test.
Activation of these zones causes the system to exit the walk test and transmit an alarm
condition to the monitoring station.
If you initiate a walk test and do not activate a zone within 15 minutes, the system automatically
exits the walk test. The system sounds for 5 minutes before the test ends.
Note: This feature is not available in CP-01 panels.
PowerSeries Pro HS3032/HS3128/HS3248 User Manual32