FORM 160.77-O2
ISSUE DATE: 11/15/2011
SECTION 3 - YKEP CONTROL PANEL OPERATION
JOHNSON CONTROLS
71
3
PRV
Access Level Required: OPERATOR
P
Allows the technician to program the proportional gain
for the temperature controller while the chiller is con-
trolling on PRV’s.
I
Allows the technician to program the integral gain
(minutes per repeat) for the PRV.
D
Allows the technician to program the derivative gain
for the PRV.
Hot Gas
Access Level Required: OPERATOR
P
Allows the technician to program the proportional gain
for the temperature controller while the chiller is un-
loaded on hot gas.
I
Allows the technician to program the integral gain
(minutes per repeat) for the Hot Gas Valve.
D
Allows the technician to program the derivative gain
for the Hot Gas Valve.
Chilled Setpoint Ramp - Ramp Rate
Access Level Required: OPERATOR
Allows the technician to program the degrees per sec-
ond ramp rate for the chilled liquid setpoint to react to
a program change.
Hot Gas - Ramp Rate
Access Level Required: OPERATOR
Allows the technician to program the percent per sec-
ond startup closure ramp rate for the hot gas valve.
PRV - Ramp Rate
Access Level Required: OPERATOR
Allows the technician to program the percent per sec-
ond startup opening ramp rate for the PRV.
IC-160A Primary Demand Limit
SP
Access Level Required: OPERATOR
Allows the user to specify the current limit value (as a
percentage of FLA) to which the chiller will be limited
during the specified pulldown limit time. This value
will override the Motor Current Limit value during this
time period. This function is used to provide energy
savings following chiller start-up.
P
Allows the technician to program the proportional gain
for the primary compressor demand limit.
I
Allows the technician to program the integral gain
(minutes per repeat) for the primary compressor de-
mand limit.
D
Allows the technician to program the derivative gain
for the primary compressor demand limit.
Pulldown Demand Limit
Access Level Required: OPERATOR
Allows the user to specify the current limit value (as a
percentage of FLA) to which the chiller will be limited
during the specified pulldown limit time. This value
will override the Motor Current Limit value during this
time period. This function is used to provide energy
savings following chiller start-up.
Pulldown Time
Access Level Required: OPERATOR
Allows the user to set a period of time for which the
pulldown demand limit will be in effect after the chiller
starts.
NAVIGATION
Previous
Causes an instant return to the previous screen
Capacity Limits
Access Level Required: OPERATOR
Causes an instant navigation to the Capacity Limits
Screen.
Capacity Controls
Access Level Required: OPERATOR
Causes an instant navigation to the Capacity Controls
Screen.
Alarm History
Causes an instant navigation to view the Alarm History
Screen.