FORM 160.77-O2
ISSUE DATE: 11/15/2011
SECTION 3 - YKEP CONTROL PANEL OPERATION
JOHNSON CONTROLS
75
3
I
Allows the user to program the integral gain (minutes
per repeat) for the Hot Gas Valve.
D
Allows the user to program the derivative gain for the
Hot Gas Valve.
PC-113 High Discharge Override
Access Level Required: OPERATOR
SP
Allows the user to program the High Discharge Over-
ride Pressure Setpoint.
P
Allows the user to program the proportional gain for
the High Discharge Override.
I
Allows the user to program the integral gain (minutes
per repeat) for the High Discharge Override.
D
Allows the user to program the derivative gain for the
High Discharge Override.
NAVIGATION
Previous
Causes an instant return to the previous screen
Capacity Tuning
Access Level Required: OPERATOR
Causes an instant navigation to the Capacity Tuning
Screen.
Alarm History
Causes an instant navigation to view the Alarm History
Screen.