Figure 4: OptiView control panel microboard (031-03630) details
HIGH PRESSURE CUTOUT SWITCH
RESERVED (MBC #2 LEVITATED)
RESERVED (HPCO SWITCH #2)
REMOTE CURRENT LIMIT SETPOINT
CHILLED LIQUID FLOW SWITCH
MULTI UNIT SEQUENCE CYCLING
AUXILIARY SAFETY SHUTDOWN
CONDENSER LIQUID FLOW SWITCH
RESERVED (MOTOR CONTROLLER #2 FAULT)
PURGE REGEN DRAIN TANK SOLENOID
COND/EVAP OIL RETURN SOLENOID VALVE
PURGE INLET SOLENOID, PURGE PUMP, PURGE PUMP SOLENOID, PURGE REGEN TANK VENT SOLENOID
RESERVED (MOTOR CONTROLLER #2 STOP)
RESERVED (MOTOR CONTROLLER #2 START)
CONDENSER LIQUID PUMP RUN
REMOTE MODE READY TO START
035-26662-000
REV E, SHT. 3
Note: See details A, B and C of Figure 5 and details D and E of Figure 6.
Wiring notes
1. If flow switches are connected to J14, microboard jumpers JP10, JP11, and JP12 must be on pins
2 and 3.
2. For VGD communication, jumpers JP27 and JP29 must be installed on pins 1 and 2.
19Unit Wiring and Field Connections for YZ Centrifugal Chiller with Magnetic Bearing Controller