4. Installation setting
JCX-161 BNWAS Installation Manual
94
7ZPNA4321
The setting range and initial value of a configuration parameter of operation
No.
Subject name Classification Parameter Memory Initial value Remarks
1
OPERATION MODE For users
AUTOMATIC
MANUAL ON
MANUAL OFF
Volatilization
MANUAL
ON
2
INTERVAL
ALARM TIME
For users
3min - 12min
1min ste
Un-volatilizing 3
3
3rd STAGE
ALARM TIME
For users
0 sec, 90 to 180sec
10sec ste
Un-volatilizing 90
4
BRIDGE ALARM
TRANSFER
For users
0 to 30sec
10sec ste
Un-volatilizing 0
5
BACKUP OFFICER For users
CAPTAIN
C/O
2nd OFFICER
3rd OFFICER
Un-volatilizing All ON
Audible alarm setting at the time
of 2nd Stage Remote audible
alarm
At least one audible alarm setting
should be ON. (don't perform all
OFF setting).
6
PASSWORD For users 0000-9999 Un-volatilizing 0000
7
CONTRAST For users 1 to 13 Un-volatilizing 5
8
DIMMER MAX For users 4 to 13 Un-volatilizing 9
9
DIMMER TYP For users 3 to 13 Un-volatilizing 6
10
DIMMER MIN For users 2 to 13 Un-volatilizing 4
11
CLICK SOUND For users ON/OFF Un-volatilizing ON Key click sound
12
BACK LIGHT For users ORANGE/WHITE Un-volatilizing WHITE
13
BUZZER SOUND For users
CONTINUOUS
ON/OFF
Un-volatilizing ON
Sound pattern setting of audible
alarm
14
Alarm history For users
AC FAIL
DC FAIL
COMM ERROR
SYSTEM FAIL
Un-volatilizing NULL It holds up to 256 pieces.
15
BackupOfficerName
(Captain)
For users
Character string up to
nine characters
Un-volatilizing CAPTAIN
16
BackupOfficerName
Chief Officer
For users
Character string up to
nine characters
Un-volatilizing C/O
17
BackupOfficerName
2nd Officer
For users
Character string up to
nine characters
Un-volatilizing 2ND
18
BackupOfficerName
3rd Officer
For users
Character string up to
nine characters
Un-volatilizing 3RD
19
BuzzerSetting CH3
For installation
ersons
ON/OFF Un-volatilizing ON
Connection / Non-connection
settin
of audible alarm unit
20
BuzzerSetting CH4
For installation
ersons
ON/OFF Un-volatilizing ON
Connection / Non-connection
settin
of audible alarm unit
21
BuzzerSetting CH5
For installation
ersons
ON/OFF Un-volatilizing ON
Connection / Non-connection
settin
of audible alarm unit
22
BuzzerSetting CH6
For installation
ersons
ON/OFF Un-volatilizing ON
Connection / Non-connection
settin
of audible alarm unit
23
BuzzerSetting CH7
For installation
ersons
ON/OFF Un-volatilizing ON
Connection / Non-connection
settin
of audible alarm unit
24
BuzzerSetting CH8
For installation
ersons
ON/OFF Un-volatilizing ON
Connection / Non-connection
settin
of audible alarm unit
25
NMEA COMM
For installation
persons
16 kinds
ALARM NO: up to 5
characters
ALARM NAME: up to
12 characters
Un-volatilizing blank
26
RMS output
For installation
ersons
ON/OFF Un-volatilizing OFF RMS output On/Off setting
27
Display serial number
For installation
ersons
7 degits, alphanumeric
character
Un-volatilizing
It holds by a display unit.
28
Display bar code
number
For installation
persons
11 degits,
alphanumeric
character
Un-volatilizing
It holds by a display unit.
29
Control unit serial
number
For installation
persons
7 degits, alphanumeric
character
Un-volatilizing
It holds by a control unit.
30
Control unit bar code
number
For installation
persons
11 degits,
alphanumeric
character
Un-volatilizing
It holds by a control unit.