5. Operation check
JCX-161 BNWAS Installation Manual
108
7ZPNA4321
5.2 Operation check of other units
Item Operation Content of check
NWZ-4650 Wait to pass dormant period. The visual indication starts. (The LCD
blinks.)
The 1st Stage Bridge audible alarm starts
in 15 seconds. (The reset button unit’s
LEDs blink short, and the buzzer sound.)
After that, press (ACK button) to stop
the alarm.
Press (dimmer) button. The brightness of LCD / operation key
changes.
Press 󲨘 (Emergency call) button
for 2 seconds.
All the buzzers of the reset button unit
/buzzer units sound.
After that, press (ACK button) to stop
their sound.
Select [OFFICER CALL] in the menu,
and then perform it.
The buzzers of the reset button unit and
backup officer’s buzzer unit sound.
After that, press (ACK button) to stop
their sound.
NCJ-895
NCJ-896
Wait to pass dormant period. The visual indication starts. (The LEDs
around the reset button blink.)
The 1st Stage Bridge audible alarm starts
in 15 seconds. (The reset button unit’s
LEDs blink short, and the buzzer sounds.)
After that, press the reset button to stop
the alarm.
Press [DIM] button. The brightness of the LEDs around the
reset button changes.
NYG-5 Cross in front of the sensor. The dormant period is reset.