8 Configuration
8.3 Generator “Pro”
Pro: (Program) Generator
The basic function of the instrument is defined here. The instrument can be operated
as a fixed-setpoint controller with or without a ramp function, or warm-up ramp for
hot-channel equipment, program controller or program generator.
Configuration
Analog inputs
Controller
Generator
Limit comparators
Outputs
Binary functions
Display
Timer
Interfaces
Symbol Value/selection Description
General
Function
Fnct
0
1
2
3
4
Fixed-setpoint controller
Ramp function
Program controller
Program generator
Hot-channel controller
Ramp function:
A rising or a falling ramp function can be implemented. The
ramp end value is determined by the setpoint input and can be
altered from the I and D keys, just as for a fixed-setpoint
controller.
The ramp function can be paused or canceled via the binary
functions.
v Chapter 8.6 “Binary functions “binF””
Program generator:
Is used, for instance, to output the setpoint profile via a
continuous output without a control function.
Settings for the program generator are not evaluated with
regard to the process value (e. g. start at process value,
continue, tolerance band).
Factory settings are shown bold.
H
The ramp function is interrupted on a probe break, or
for manual mode. The outputs react as for overrange/
underrange (configurable).