8 Configuration
Acknowledgement
AcnL
0
1
2
no acknowledgement
acknowledgement; only with inactive limit comparator
acknowledgement; always possible
For settings with acknowledgement, the limit comparator is
latching, which means it remains ON, even when the switch-
on condition is no longer present.
The limit comparator must be reset via the D + X keys or
binary signal.
Pulse time
tPuL
0 9999s The limit comparator is automatically reset after an adjustable
time period.
Limit comparator PV
LCPr
(analog selector)
process value
see circuit diagrams
Limit comparator SP
LCSP
(analog selector)
present setpoint
see circuit diagrams (only with lk1lk6)
Hysteresis function (setup) symmetrical
asymmetrical, left
asymmetrical, right
see circuit diagrams
v Chapter 12.2 “Alarm messages”
Limit comparator 1 LC1
Limit comparator 2 LC2
Limit comparator 3 LC3
Limit comparator 4
LC4
Symbol Value/selection Description
Factory settings are shown bold.
Analog selector
0 no function 21 program run time in sec
1 analog input 1 22 residual program time in sec
2 analog input 2 23 segment run time in sec
3 process value 24 residual segment time in sec
4 present setpoint 25 timer run time for timer 1 in sec
5 ramp end value 26 timer run time for timer 2 in sec
6 program setpoint 27 residual run time for timer 1 in sec
7 math 1 28 residual run time for timer 2 in sec
8 math 2 29 present segment end value
9 setpoint 1 30 analog marker (Profibus)
10 setpoint 2 31 reserved
11 setpoint 3 32 reserved
12 setpoint 4 33 reserved
13 controller output level
14 controller output 1
15 controller output 2