Option Option code Exists?
Heat recovery ΔT=55 K W3
Tab. 3 Options
2.3 Weight
The weight given is the maximum. The actual weight of individual machine is dependent on equipment
fitted.
ASD 25 ASD 30 ASD 40S ASD 40
Weight [lb] 3640 4040 4080 4320
Tab. 4 Machine weight
2.4 Temperature
ASD 25 ASD 30 ASD 40S ASD 40
Minimum cut-in tempera‐
ture [°F]
40 40 40 40
Typical airend discharge
temperature during opera‐
tion [°F]
167–200 167–200 167–200 167–200
Maximum airend dis‐
charge temperature (auto‐
matic safety shut-down)
[°F]
230 230 230 230
Tab. 5 Temperature
2.5 Ambient Conditions
ASD 25 ASD 30 ASD 40S ASD 40
Maximum elevation* [ft.] 3000 3000 3000 3000
Permissible ambient tem‐
perature [°F]
40–115 40–115 40–115 40–115
Cooling air temperature
[°F]
40–115 40–115 40–115 40–115
Inlet air temperature [°F] 40–115 40–115 40–115 40–115
Maximum relative humidi‐
ty of inlet air
see figure 1 see figure 1 see figure 1 see figure 1
* Higher altitudes are permissible only after consultation with the manufacturer
Tab. 6 Ambient Conditions
2 Technical Data
2.3 Weight
4
Service Manual Screw Compressor
ASD T Tri-Voltage 9_5721 06 USE