Compressed air system
ABT 37 ABT 57
Pressure drop [psi]
(in relation to 100 psig
working pressure)
3 3
Maximum permitted work‐
ing pressure [psig]
230 230
Tab. 28 Refrigeration dryer: compressed air system
Refrigerant circuit
ABT 37 ABT 57
Refrigerant R134a R134a
Global warming potential
(GWP)
1300 1300
Charge quantity* [lb]
Maximum permitted work‐
ing pressure [psig]
305 305
Safety pressure switch:
shutdown pressure [psig]
305 305
* Read off the charge quantity from the dryer nameplate and enter it in the table.
Tab. 29 Refrigeration dryer: refrigeration circuit
2 Technical Data
2.16 Refrigeration dryer
9_5721 06 USE