Setup H 6-AFE
FW 1.2 / 1.4
Supply t h e AFE only wit h 24V!
(24V- and charging Unit or H6 PLC
with power su pply connecte d to
mains)
Com mu nic ati on
established?
yes
downl o ad Filt er_Dow nl oa dl ist
in AFE unit
Plug X2A, X2B di sco nnec t
Error
Fil te r_Downl oa dl ist
according to curent H W
available?
DC Link capacity all am DC Link connected Units add and in
AFE Uni t store.
cu17: … µF
these „alert“ occurs, beca use t he list
was created on a different device.
Voltage on the DC li nk at this point c an dam age
the de vic e!
See installation instructions electric shock
no
no
yes
the DC Lin k c ap aci ty of the co nnec te d device c an be
foun d In pa ram et er: de35 or the programming guide
set:
dr05, dr06
Basic settings, AC power supply
e.g..: dr05, mains voltage , 400V
dr06, line frequency , 50Hz
http://www .keb.de/de/
service-dow nl oads/
downl o ads
set: Is10 := dr53
(Switching frequency AFE Filter)
Only partial load operation is
poss ible!
no
yes
Other lines of communication between PC and
AFE are also possible.
answer message false configuration with „yes“
de15 := 0 ?
set
co08 := 2 Device i s reset to factory settings!
Done
is ru14
≈
cu21
1)
and
st12 = 5?
Requireme nt:
Hardware circuit ele ctrically checke d!
Ap pl icati on mee ts t he mains c onne ct ion
requireme nt s!
Che ck i f H6-AFE device
(device type: No de_1_H6_ac ti ve _fro nt_end)
set
co09 := 1
wrong unit!
yes
no
co09 = counts up,
co09 = 0?
Restart drive, commu ni cation lost!
dr49..dr53 according to HW
switching frequency is included
Interne t
available?
copy LCL Filter data
dr15, dr17,
dr49-dr53,
dr65-dr66.
is dr02 =2?
no
yes
no
yes
Plug X2A, X2B
disconnect
control word co00 := 0
Rese t deletes all data
(Also operating hours, etc.)
See programming manual -> LCL filter
Data stored?
control word co00 := 11
ST with control
wor d?
set I2
set
dr15 an d dr17
is dr02 = 2?
set dr99 := 0
Data stored!
no
yes
1
2
3
4
5
6
7
9
10
11
12
13
14
15
16
17
18
19
20
26
27
28
29
30
31
32
33
34
35
37
yes
no
Presets are included in filter
Downl oa d
save da ta!
no
yes
is line inductance
&netw ork re sis tance
known?
set control word
dr99 := 0
set co00 := 3
no
yes
or
set I2 b ack
38
39
40
42
43
44
45
46
ST OFF
DC li nk dis charged
data saved?
ST
precharging on
control word co00 := 3
Switching frequency AFE> = switching
frequency of AFE filter!
check and set cu21
1)
(DC-vol ta ge), see program mi ng gu id e
DC-Bus PID -> Set point
commissioning at
costumer site?
no
yes
on site co mmiss ioni ng
47
48
50
49
set
cu99 := 4
accordi ng to t he ap pl icati on,
optimize the voltage PID
is is10 >= dr53?
no
yes
the input of voltage set point is adapted immediately.
the DC cont rol vo ltage i s, for example, at 400V (AC) min.
680V (DC).
yes
no
Final commissioning on site
after delivery to the customer!
commissioning at cus tomer
si te?
dr12 := rated curre nt of M CB /
de28 * 10 0%
Commissioning under test environment
de28 de29 dr12
is the mains supply > =
rated device power?
Modulation off
Pre ch arging off
Com mi ssi onin g w it h
mains i dentification
no
yes
yes
no
is the AFE-rated current
de28 <= rate d filter
curr ent?
set
dr12 := max Filter current / de28
* 10 0%
51
53
52
55
54
Step by step setup H6 AFE
yes
no
is max AFE Filter current <
de29
in dependence on the
cooli ng of the AFE / LCL fi lt er
part l oa d is possible
Is t he ap pa rent c urrent
limited?
dr12:= max curre nt applic ation /
de28 * 100%
In dependence on the cooling of the
AFE, a partial load operation is possible
See sub procedure
identifi cation
set dr12:= de29 / de28 * 100%
Data can be fo und in the rel evant
installation manual
AFE/ LCL Filte r
maxi mum relat ive
filter current
Rated filter current (IN)
maxi mum fil ter curre nt (IMAX)
8
no
yes
decision acti on
st art / end
comment
questi on
is sue
Explanation:
ex te r nal HW
Note:
These commissioning instructions should be read and executed from left to right from top to
bottom. The direction of the arrow gives the sequence of the individual steps. The order is
important! Some settings are based on other settings, which need to be set in advance.
1) With software V1.4 the setpoint of the control voltage "Target Uic" is indicated in parameter
IDText cu18 instead of parameter cu21.
56
column numb er
21
22
23
24
25
36
41
Version: 1.1 / 05.05.2020
COMBIVIS with USB Adaptor
connect ed t o AFE
Ethernet Adaptor
or
Impor t ant !
charging maximum load / relative current value.
yes
no
set is10 := AIC rated switching
frequency
Important otherwise overcurrent fault!
AFE ra ted s wi tc hi ng freq ue nc y
(See installation manual for technical
data)
Connector X2A, X2B
Plug in
Set HW ST
final f un ct ion te st
set point vol tage reac he d and A FE
modul ate s?
56