EasyManua.ls Logo

Keithley 6482 - Remote Versus Local Operation; Local-To-Remote Transition; Remote-To-Local Transition; Selecting an Interface

Keithley 6482
350 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12-2 Return to Section Topics 6482-901-01 Rev. A / August 2012
Section 12: Remote Operations Model 6482 Dual-Channel Picoammeter / Voltage Source Reference Manual
Remote versus local operation
This topic summarizes remote operation enhancements and local-to-remote and remote-to-local
transitions.
Local-to-remote transition
When changing from local-to-remote operation, the following takes place:
The Model 6482 stops taking readings and is placed into the idle layer of the trigger model.
All menus are exited.
All pending front-panel commands are aborted.
The reading buffer is cleared; FETCh?, CALC1:DATA?, and CALC2:DATA? will not return
any data until the Model 6482 takes readings while in remote operation.
All other settings remain unaffected, including TRACe buffer storage.
Sources are placed in the FIXed mode.
Remote-to-local transition
When changing from remote-to-local operation, the following takes place:
The Model 6482 stops taking readings and is placed into the idle layer of the trigger model.
All user-defined displays are disabled.
The display is re-enabled if it was previously turned off.
Readings are continuously taken.
Sources are placed in the FIXed mode.
Selecting an interface
The Model 6482 supports two built-in remote interfaces:
GPIB (general purpose interface bus)
RS-232 interface
You can use only one interface at a time. The factory interface selection is the GPIB bus. You can
select the interface only from the front panel. The interface selection is stored in nonvolatile
memory; it does not change when power has been off or after a remote interface reset.
The GPIB bus is the IEEE-488 interface. You must select a unique address for the Model 6482.
The address is displayed when the instrument is turned on. At the factory, the address is set to 25.
The IEEE-488 address can only be changed from the front panel while the IEEE-488 bus is
enabled.
The RS-232 interface is a serial interface. Programmable attributes of the RS-232 interface
include the following (factory default settings are shown in parentheses):
Baud rate (9600)
Data bits (8)
Parity (none)
Terminator (CR)
Flow control (none)
RS-232 settings for baud rate, parity, and data bits are accessible only from the front panel while
RS-232 is enabled.

Table of Contents

Related product manuals