9.3.4 Cleaning the condenser
9.3.4.1 Air-cooled condenser
The SmartCool System refrigerating machine operates largely without servicing.
So that the full cooling power is available, the heat exchanger (condenser) should cleaned of dust at
intervals of one month or longer depending on the operating period and dust level in the ambient air.
To do this, open the front grille, brush off the condenser and,
where necessary, blow over with compressed air.
Extreme contamination is detected by the Proline SelfCheck
Assistant, which then issues a warning.
9.3.4.2 Water-cooled condenser
9.3.4.2.1 Cleaning the dirt trap
At regular intervals of one month or lo
nger, the dirt trap must be cleaned, depending on the degree of
soiling.
Take off the water feed hose on the device
and remove the filter. Clean the filter and
insert it again into the cooling water feed.