Parameterising analog modules
Signal functions of 4xanalog input
12
Parameter setting via system bus (CAN) / CANopen
12.3
12.3.5
L
12.3−8
EDSPM−TXXX−9.0−11/2009
12.3.5 Signal functions of 4xanalog input
) Note!
l Short−circuit unused inputs (connect positive and negative
terminals) or deactivate them by assigning the function number
FF
h
.
l In the event of an overflow or underflow, wrong values are
output. Strong signal jumps with sign reversal may occur.
I/O system IP20 multiplies measured values with decimal positions and without
normalisation by a factor and transfers them as integers to the bus. To output the
decimal positions, divide the measured values by the same factor.
Example:
Measuring task: Temperature measurement with signal function 01
h
. Measured value = 80.5 °C.
1. I/O system IP20 converts the measured value into an integer:
80.5 [°C] × 10 = 805
2. Reconvert the measured value to output it with decimal positions:
805[°C]
10
+ 80.5°C
Paramete
r bytes
2/3/4/5
Signal function Signal range Format
1)
Tolerance
2)
00
h
10 Parameter data in module are not overwritten
01
h
Temperature
measurement with
two−wire
connection
PT100 −200.0 {0.1 °C} +850.0
S7
Two’s
complement
±1 °C
3)
02
h
PT1000 −200.0 {0.1 °C} +500.0
03
h
NI100 −50.0 {0.1 °C} +250.0
04
h
NI1000 −50.0 {0.1 °C} +250.0
05
h
Resistance
measurement with
two−wire
connection
60 W 0.00
0
{0.01 W}
{1
dec
}
+60.00
32767
S7
±0.2 % of the
final value
3)
06
h
600 W 0.00
0
{0.01 W}
{1
dec
}
+600.00
32767
07
h
3000 W 0.00
0
{0.01 W}
{1
dec
}
+3000.00
32767
08
h
6000 W 0.00
0
{0.01 W}
{1
dec
}
+6000.00
32767
09
h
Temperature
measurement with
four−wire
connection
PT100 −200.0 {0.1 °C} +850.0
S7
Two’s
complement
±0.5 °C
0A
h
PT1000 −200.0 {0.1 °C} +500.0
0B
h
NI100 −50.0 {0.1 °C} +250.0
0C
h
NI1000 −50.0 {0.1 °C} +250.0
0D
h
Resistance
measurement with
four−wire
connection
60 W
0.00 {0.01 W} +60.00
S7
±0.1 % of the
final value
0 {1
dec
} 32767
dec
0E
h
600 W
0.00 {0.01 W} +600.00
S7
±0.05 % of
the final value
0 {1
dec
} 32767
dec
0F
h
3000 W
0.00 {0.01 W} +3000.00
S7
±0.05 % of
the final value
0 {1
dec
} 32767
dec
10
h
Temperature
measurement with
thermoelement and
external
compensation
4)
Type J −210.0 {0.1 °C} +850.0
S7
Two’s
complement
±1 °C
11
h
Type K −270.0 {0.1 °C} +1200.0 ±1.5 °C
12
h
Type N −200.0 {0.1 °C} +1300.0 ±1.5 °C
13
h
Type R −50.0 {0.1 °C} +1760.0 ±4 °C
14
h
Type T −270.0 {0.1 °C} +400.0 ±1.5 °C
15
h
Type S −50.0 {0.1 °C} +1760.0 ±5 °C

Table of Contents