24 V supply for motor holding brake
Terminal X107: supply voltage brake + / - 24B,
GB
DC supply of X106
External power supply unit
specic
aon
SELV/PELV
Rated input voltage V +24 ± 20 %
Max. Input current 0.37 ... 15 kW A 2.5 Typical: according to the load at X106
22 ... 110 kW A 5.0
Polarity reversal protecon Yes
Suppressor circuit Yes Suppressor diode 30 V, bidireconal
Connecon descripon Motor brake 24 V supply for motor brake
Connecon X106 X107
Connecon type Pluggable Pluggable
Max. cable cr
oss-secon mm² 1.5 2.5
Max. cable cross-secon AWG 16 12
Stripping length mm 9 10
Stripping length in 0.35 0.39
Required tool Screwdriver 0.4 x 2.5 Screwdriver 0.6 x 3.5
Brake resistor c
onnecon
Use intrinsically safe brake resistors to be able to dispense with a separate
s
witch-o device (e.g. a contactor).
Short c
onnecon cables up to 0.5 m Long connecon cables up to max. 5 m
Up to a cable length of 0.5 m, the cable for the brake resistor and that of
the temperature monitoring can be twisted. Doing so reduces problems
due to EMC interference.
The cable of the brake resistor must be shielded.
The maximum length is 5 m.
Twisng is sucient for the temperature monitoring cable.
① Wiring to the "brake resistor" c
onnecon on the inverter or another component with brake chopper.
② Oponal: Wiring to a control contact that is set to monitor the thermal contact.
If the thermal contact responds, the voltage supply to the inverter must be disconnected (e.g. switch o the control of the mains
contactor).
Electrical ins
tallaon
Brake resistor connecon
153