Absicherungsdaten
Br
anch Circuit Protecon (BCP)
Short Circuit Current Rangs (SCCR) with Standard Fuses and Circuit Breaker
(Tested per UL61800-5-1, reference UL le E132659)
These devices are suitable for motor group installaon when used with Standard Fuses or Cir-
cuit Breaker. For single motor installaon, if the fuse value indicated is higher than 400 % of
the motor current (FLA), the fuse value has to be calculated. If the value of the fuse is below
two standard rangs, the nearest standard rangs less than the calculated value shall apply.
Inverter Standard Fuses (UL248) Circuit Breaker (UL489)
Mains Rated power
Max.
SCCR
Max. rated current Class
Max.
SCCR
Max. rated current Min. cabinet dimensions
kW hp kA A kA A m³ ³
230 V, 1/3-ph 0.37 0.5 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 1/3-ph 0.55 0.75 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 1/3-ph 0.75 1 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 1/3-ph 1.5 2 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 3-ph 2.2 3 65 35 CC, CF, J, T 65 25 0.042 1.48
230 V, 3-ph 4 5 65 60 CC, CF, J, T 65 60 0.042 1.48
230 V, 3-ph 5.5 7.5 65 60 CC, CF, J, T 65 60 0.042 1.48
480 V, 3-ph 0.55 0.75 65 35 CC, CF, J, T 65 25 0.042 1.48
480 V, 3-ph 0.75 1 65 35 CC, CF, J, T 65 25 0.042 1.48
480 V, 3-ph 2.2 3 65 35 CC, CF, J, T 65 25 0.042 1.48
480 V, 3-ph 4 5 65 35 CC, CF, J, T 65 25 0.042 1.48
480 V, 3-ph 7.5 10 65 60 CC, CF, J, T 65 60 0.042 1.48
480 V, 3-ph 11 15 65 60 CC, CF, J, T 65 60 0.042 1.48
480 V, 3-ph 15 20 65 60 CC, CF, J, T 65 60 0.042 1.48
480 V, 3-ph 22 30 65 70 CC, CF, J, T 65 70 0.17 6
480 V, 3-ph 30 40 22 125 CC, CF, J, T 35 125 0.57 20
480 V, 3-ph 45 60 22 125 CC, CF, J, T 35 125 0.57 20
480 V, 3-ph 55 75 22 200 CC, CF, J, T 35 200 0.57 20
480 V, 3-ph 75 100 22 200 CC, CF, J, T 35 200 0.57 20
480 V, 3-ph 90 125 22 300 CC, CF, J, T 10 300 0.57 20
480 V, 3-ph 110 150 22 300 CC, CF, J, T 10 300 0.57 20
Short Circuit Current Rangs (SCCR) with Semic
onductor Fuses
(Tested per UL61800-5-1, reference UL le E132659)
These devices are suitable for standard installaon when used with Semiconductor Fuses. For
single motor installaon, if the fuse value indicated is higher than 400 % of the motor current
(FLA), the fuse value has to be calculated. If the value of the fuse is below two standard
rangs, the nearest standard rangs less than the calculated value shall apply.
Elektrische Ins
tallaon
Anschluss nach UL
Absicherungsdaten
41