Inverter I95AE
322F 330F 345F 355F 375F 390F 411F
Rated power P
r
ated
kW 22 30 45 55 75 90 110
Rated power P
rated
hp 30 40 60 75 100 125 150
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 - 400/480 V
Rated mains current
without mains choke -
with mains choke 42 54.9 80 99 135 168 198
Apparent output power kVA 32 41 60 75 100 121 142
Rated output current
2 kHz A 47 61 89 110 150 180 212
4 kHz A 47 61 89 110 150 180 212
8 kHz A 47 61 89 110 150 162 191
16 kHz A 31.3 40.6 59.3 76.6 95 99 106
Power loss
2 kHz W 505 653 934 1151 1553 1855 2177
4 kHz W 536 694 994 1224 1654 1975 2319
8 kHz W 694 898 1292 1593 2157 2326 2731
16 kHz W 694 898 1292 1593 2157 2326 2731
Cyclic mains switching 3 mes per minute
Max. motor cable length
shielded
without EMC category m 100 200
Category C1 (2 kHz, 4 kHz,
8 kHz)
m -
Category C2 (2 kHz, 4 kHz,
8 kHz)
m 20
Category C3 (2 kHz, 4 kHz,
8 kHz)
m 35 100
Weight m kg 10.7 16.7 24 35.6
Weight m lb 23.6 37 53 78.5
Technical data
3-phase mains c
onnecon 400 V
Rated data
177