Service Manual 163
Specifications
Heat Pump (50Hz)
1.1.2 Heat Pump
Model Unit
W
Cooling Capacity kcal/h
Btu/h
W
Heating Capacity kcal/h
Btu/h
Dimensions (W*H*D)
Body
mm
inch
Coil
Rows x Columns x FPI
Face Area m
2
Type
Motor Output W
Running Current A
Fan Air Flow Rate(H/M/L) cmm
cfm
Drive
Speed control
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side mm(inch)
Pipe Connections
Gas Side mm(inch)
Drain Pipe(ID)
mm
Net Weight kg(lbs)
Noise Level
(Sound Press,1.5m, H/M/L)
dBA±3
Power Supply Ø / V / Hz
Refrigerant Control
Power cable mm
2
Transmission cable mm
2
Front Panel('*' Position)
Stuffing Quantity Without S/parts
20/40ft
LRNN126SV*0 LRNN186SV*0
3,500 5,300
3,009 4,557
11,942 18,084
3,938 5,963
3,385 5,127
13,435 20,345
928*522*147 928*522*147
36.5*20.6*5.8 36.5*20.6*5.8
2*16*20 2*16*20
0.24 0.24
Turbo Fan Turbo Fan
20x2 20x2
1.3x2 1.3x2
8.6 / 8 / 7.3 13.5 / 11.4 / 10.4
304/283/258 477/403/367.5
Direct Direct
BLDC BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene
Accessory Accessory
Fuse Fuse
Ø9.52(3/8) Ø9.52(3/8)
Ø15.88(5/8) Ø15.88(5/8)
20 20
15(33) 15(33)
43/42/40 46/43/42
1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50
LEV LEV
CV2.0 X 3C CV2.0 X 3C
CVV-SB 1.25 X 2C CVV-SB 1.25 X 2C
M:Metal, B:Blue, D:Wood
180/378 180/378
Conversion Formula
Kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
Notes:-
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. L.E.V.: Linear Expansion Valve