212 Outdoor Unit
Function
2.4.3 Stopping operation of sub units when only main unit operates
Fan
Main LEV
4way valve
Subcooling LEV
Depends on
main unit fan frequency
Full open(cooling)
SH control(heating)
Same state to main unit
Subcooling control(cooling)
min. pulse(heating)
OperationComponent
Sub unit ’s
compressor
Off
Hot gas bypass
Normally Off