80 Indoor Unit
Functions
2. Functions
Indoor Unit
Duct-Low
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Soft Dry Operation Mode
Deice (defrost) control (Heating)
Auto Restart
Hot-start Control (Heating)
• The indoor fan does not rotate until the evaporator piping
temperature reaches 25°C.
High head height Drain pump
• A standard drain-head height of up to 700mm is possible.
Central Control(Optional)
•
It is operating individually or totally by central control function.
• Room temperature sensor. (Thermistor)
•
Maintains the room temperature in accordance with the Setting Temperature.
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is inhibited for approx. 3 minutes.
• High, Med, Low
• Intermittent operation of fan at low speed.
• Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
• Both the indoor and outdoor fan stops during defrosting.
• Hot start after defrost ends.