208 Outdoor Unit
Function
■ Ending condition
1) All Heat exchanger pipe temperature are above 15˚C
2) Defrost running time is over 20 min.
3) liquid injection begins
2.3 Oil equalizing control
2.3.1 Oil equalizing control on cooling mode
■ Ending condition
1) 4min after control begins