214 Outdoor Unit
Function
3.1.2 Pressure control on heating mode
High pressure control
Low pressure control(above -10˚C)
2108kPa <Pc 2441kPa
High pressure
control
5Hz down/sec
No frequency up
5Hz down/sec
System stop
2441kPa <Pc 2657 kPa
Pc>2657kPa
Pc 2108kPa
High pressure
control
Low pressure
control
Pressure range Compressor Fan
-
-
-
Hot gas
bypass
49 kPa< Pe 62kPa 5Hz down/sec
No frequency up
5Hz up/sec
Low pressure
control
System stop
62kPa< Pe 101kPa
Pe >101kPa
Pe 49 kPa
High pressure
control
Low pressure
control
Pressure range Compressor Fan
-
-
-
Hot gas
bypass