EasyManua.ls Logo

LG multi V PLUS

LG multi V PLUS
373 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service Manual 275
Self-diagnosis function
Fault diagnosis and Trouble shooting guide
Error Item
Error
Display No.
Major Error Occurrence CauseMeaning
Sensor error Abnormal measuring
value of sensor
(Open/Short)
Defective temperature sensor (open/short)
Defective PCB.
No
Connect to the terminal.
Yes
Replace the sensor.
Is connection status normal?
No
Yes
Is sensor resistance value normal?
Check or replace the PCB.
Check connection status of the sensor.
Trouble shooting Flow
40, 41, 42, 43, 44,
45, 46, 47, 48, 65,
113, 114, 115, 116,
117, 118, 120, 121,
122, 123, 124, 125,
126, 127, 128, 129,
130, 132, 133, 134,
135, 136, 137, 138,
139, 148
* See the Temperature Resistance Table

Table of Contents

Related product manuals