116 
 
Saves the frequency command from Up/Down 1 or Up/Down 2. Up/Down 1 and Up/Down 2 
cannot be used at the same time. If a multi-function input terminal is assigned to Up/Down 1 
and Up/Down 2, an alarm will be triggered.   
This parameter is enabled in the following situations.   
1.  b1-00 (Frequency  Command Selection 1)  or  b1-07  (Frequency  Command  Selection 2)=2 
(Terminal Up/ Down) 
2.  E1-□□= 10/11 ( Up/Down Command) or E1-□□= 12/13 ( Up/Down 2 Command) 
3.  L4-00 (Frequency Command Hold)= 1 or 2 (Enabled) 
The Up/Down Frequency Command Save can also be given when a Stop command is entered.   
  L4-04  Frequency Command Hold   
This  parameter  is  enabled  when  any  multi-function  terminal  is  assigned  to  E1-□□=  18 
(Acc./Dec. Ramp Hold) 
Determines  whether  or  not  to  save  the  frequency  command  when  the  Stop  command  is 
entered or the power supply is shut off.   
0 : Disabled   
The frequency command will be reset to 0 Hz when the Stop command is entered or the drive 
power supply is shut off. The active frequency command will be the drive uses when the drive 
restarts.   
1 : Enabled   
The frequency command will be saved when the Run command is removed, and remain active 
when the drive restarts. However if  the input terminal assigned  to  E1-□□= 18 is open  when 
applying the power supply, the saved frequency command will be reset to 0 Hz.