155 
 
frequency.     
2 : Output Frequency Lower Limit 
The output frequency lower limit can be adjusted by the analog input value.   
3 : Auxiliary Frequency Command 
Sets the auxiliary frequency command 1 when multi-step speed operation is selected. Refer to 
L1-00~L1-16 on page 108  ?   
4 : Output Voltage Bias 
Voltage bias increases the output voltage of the V/F characteristics as a percentage of 200V or 
400V  depending  on  the  power  supply.  This  function  is  only  available  in  the  V/F  Control 
method.   
5 : Acc./Dec. Time Gain (Decrease Only)   
Adjusts the gain for acc./ dec. time assigned to C1-00 to C1-07.   
When  the  acceleration  time  is  assigned  to  C1-00,  the  drive  acceleration  time  is  calculated 
below.   
Acc. Time = C1-00 Acc. time  ×  Acc./dec. time gain 
100%
0
10 V
10%
5 V
20%
50%
1V 2V
Acc./Dec. gain from 1 to 10 V
=                                       ╳  10 (%)
( 10 V )
Input voltage ( V )
 
Figure 6.64 Acc./Dec. Time Gain Using Analog Input 
6 : DC Braking (DB) Current 
Adjusts the DC braking current by the analog input value.     
When 10 V voltage or 20 mA current is input, the braking current  will  be 100% of the drive 
rated output current. The actual DC braking current is determined by the analog input value or 
the b2-01 value whichever is smaller.