156 
 
100%
Drive rated current
0
( 4mA ) 
10 V
( 20mA )
DC braking current level
 
Figure 6.65 DC Braking Current Using Analog Input 
7 : Stall Prevention Level During Run 
Adjusts  the  stall  prevention  level  by  the  analog  input  signal.  The  stall  prevention  level  is 
determined by the analog input value or the P3-06 value whichever is smaller.     
100%
Analog input level
0
( 4mA ) 
10 V
( 20mA )
Stall prevention level during Run
30%
3 V
( 8.8mA )
 
Figure 6.66 Stall Prevention Level Using Analog Input 
8 : PID Feedback 
Sets the PID feedback by the analog input value. To use this function, enable the PID control in 
b5-00. Refer to b5-11 on page 79   
9 : PID Target 
Sets the PID target value by the analog input value. The frequency command entered by the 
command source selected in b1-00 (Frequency Command Selection 1) is disabled. To use this 
function, enable the PID control in b5-00. Refer to b5-11 on page 79 for details. 
10:    Differential PID Feedback