160
Period
measurement
Gain, bias
RP
E5-02
E5-03
100%
0%
E5-00
E5-04
1
1 + sT
E5-01 input scaling
= 0
= 1
= 2
Pulse train
Main
frequency
command
PID
feedback
PID target
Filter time
Figure 6.70
E5-00 Pulse Train Input Function Selection
Sets the function for pulse train input terminal RP.
No.
Name
Setting Range
Default
E5-00
Pulse Train Input Function Selection
0 to 2
0
0 : Frequency Command
If the frequency command is set to pulse train input (b1-00=4 or b1-07=4), the drive will use
the frequency command from terminal RP.
1 : PID Feedback
The PID feedback value is entered to terminal RP as a pulse signal. Refer to b5-11 on page 79
for details .
2 : PID Target
The PID target value is entered to terminal RP as a pulse signal. Refer to b5-11 on page 79 for
details .
E5-01 Pulse Train Input Scaling
Sets the frequency equal to 100% frequency in Hz.
No.
Name
Setting Range
Default
E5-01
Pulse Train Input Scaling
100 to 32000 Hz
1440 Hz
E5-02 Pulse Train Input Gain
Sets the level of the input gain to terminal RP.
No.
Name
Setting Range
Default
E5-02
Pulse Train Input Gain
0.0 to 1000.0%
100.0%
E5-03 Pulse Train Input Voltage Bias
Sets the level of the input voltage bias when no signal (0Hz) is input to terminal RP.